| EY-AS422: modu422 - Automation Station
Your advantage for energy efficiency Local plant data logging enables the analysis of energy consumption and ongoing optimisation. Integrated calendar functionality enables requirement-adapted plant operation with the lowest possible energy consumption.
Areas of use Utilisable for various purposes such as fan coil, chill beam control, light control, heat pumps, ventilation systems or roof-top units.
Properties
- Compact, freely programmable LON automation station
- Supports LONMARK object types #0, #1, #3, #20020, #3300 and #20100
- LONMARK certified pursuant to Interoperability Directive Version 3.4
- Separable lower housing for separate installation of terminals and electronic components
- Audio jacks for fast access to the LON network
- LNS plug in for simple function configuration
- EY-AS422F002 with manual operating level for switching between manual and automatic operation.
Technical description
- Voltage supply 24 V~/=
- Universal inputs and outputs configurable with software
- 12 universal inputs
- 12 fused universal outputs
- 4 scheduler objects
- 128 k Flash memory for up to 12'000 event entries
- Real Time Clock
- TP/FT 10, 78 Kbps
- Neuron 3150 processor
|