RXP 210: Air-volume alarm unit

Areas of application
Monitoring laboratory fume cupboard as per EN14175 in combination with an air-volume controller, type RLP100 F123, and the RXP 212 fume cupboard operating unit. Zone 1 potentially explosive areas.

Properties

  • Comparison of sash opening setpoint with actual value of air volume
  • Feeding setpoint difference to alarm unit
  • Acoustic alarm in the event that the actual value falls below or exceeds the specified value
  • Thermoplastic housing suitable for wall or top-hat rail mounting (rail EN 60715)
  • Compressed-air connections with Rp 1/8" female thread
  • Low-pressure connections in form of stepped nipples for flexible plastic hose (internal Ø 4 and 6 mm)
  • ATEX certification for use in Zone 1 potentially explosive areas
  • Conformity tested as per EN 13463-1 and EN 1127-1 (Ex II 2 G T6)
  • Complies with directive 97/23/EC Art. 3.3 on pressure equipment


Technical description

  • Supply pressure 1.3 bar ± 0.1
  • Response sensitivity 1%

Type

Title

RXP210F001

Pneum. VAV alarm unit;