| ASM 105L, 115L: Damper drive (SUT) with LON
How energy efficiency is improved Torque related cut-off for efficient energy use.
Areas of application For use in a LON network with connection of active sensors, actuator, switch contact and passive temperature sensor. For actuation of air, shut-off and restrictor dampers and louvres.
Properties
- 5 and 10 Nm torque and holding torque
- 24 V~/=
- 35/60/120 sec. as running time for 90° can be selected in the case of ASM 105L and 60/120 sec. in the case of ASM 115L
- Protection classIP54, horizontal
- Operating noise < 30 db(A)
- Self-centring axle adaptor
- Gearbox that can be disengaged for positioning the damper and manual adjustment
- Stepping motor with control and electronic cut-off
- Maintenance-free
- Intelligent rotation angle adaptation, incl. adaptation of feedback
Technical description
- Two-part housing made of self-extinguishing plastic, lower section black and upper section yellow
- Suitable for all installation positions
- Connecting cable 1.2 m long, 5x 0.5 mm² and 6x 0.5 mm²
- Profile as per LONMARK #8110
- LON communication bus FTT 10
- On/Off switching input
- Input temperature sensor Ni1000, -50°C to +150°C
|