| EXR 560: Measuring amplifier
How energy efficiency is improved Conversion of a passive signal (e.g. outside temperature) into an active signal so it is better suited to multiplication and therefore several controllers can be made available for the energy-saving operation of the particular systems (e.g. for summer compensation).
Areas of application Amplification and inversion of actual value and control deviation signals of products in the flexotron® and equitherm® ranges.
Properties
- Setting options for start of range and span
- Optional inversion of output signal
- Depending on the connected load, the output automatically switches to current or voltage signal
Technical description
- Light-grey 140 x 65 mm housing made of thermoplastic
- Analogue input Ni200, 6.2 mV/K, 0.5 V/K or 0.6 V/K
- Output 0 -10 V, 4 - 20 mA or 6.2 mV/K
- Suitable for wall mounting
- Electrical connection with screw terminals for wires up to 2.5 mm²
|