EGP 100: Transducer for differential pressure

How energy efficiency is improved
Enables precise measurement of room pressures, duct pressures or air volumes for optimisation of energy consumption in ventilation systems.

Areas of application
Recording extremely low differential pressures and air volumes in air-conditioning, medical and environmental technology as well as in laboratories and clean rooms. Optimised for applications such as filter monitoring, room or duct pressure monitoring, fluid level monitoring, control of frequency converters for fan and air volume control, particularly for air balancing in laboratories.

Features

  • Precise recording of positive, negative and differential pressures of gases
  • Easy to combine with the XAFP100 dynamic-pressure sensor for precise air volume control
  • Capacitive-type, static double-membrane pressure sensor
  • Any installed position is possible
  • Can be used for air that contains dust or that is contaminated with chemicals (no ATEX certification)
  • Calibration certificate ex works
  • Optimal adjustment of the measuring range to suit the application
  • Adjustable zero point and filter time constant for suppression of pressure surges in the system
  • Display showing actual value and signal progression (depending on type)
  • Status LED for immediate recognition of operating status (depending on type)
  • Fitted to either wall or top-hat rail (EN 60715)
  • Cover can be opened without special tools


Technical description

  • Supply voltage of 24 V~/= (resistant to short circuit and voltage reversal)
  • Measuring ranges ±Δp
    • ±75 Pa
    • ±150 Pa
  • Measuring ranges ±Δp
    • 0...150 Pa
    • 0...300 Pa
  • Measuring range reducible to 1/3 (depending on type)
  • Constant output signal in the range of 0...10 V
  • Electrical connection via screw terminals for cables up to 1.5 mm²
  • M16 cable gland
  • Pressure connection for measuring hoses with internal Ø of 6 mm
  • Housing made from PC/ABS

Type

Title

EGP100F301

Diff.pressure transducer;150Pa,0...10V,l in

EGP100F401

Diff.pressure transducer;300Pa,0...10V,l in